Standard Linen chute for Loose Laundry |
Standard Linen Chute for Laundry Bags |
Standard 610 mm Rubbish Chute |
-
Chute to be fabricated of 16 gauge satincoat or stainless steel.
-
610mm in diameter with standard 254mm throat.
-
Fully assemble chute at the factory for installation.
-
Maximum of two sections per standard floor height.
-
Provide one expansion join per floor height.
-
Crimped joints are strictly prohibited.
-
All vertical seems shall be welded.
-
All doors attached to chute throats before delivery to jobsite.
|
-
Chute to be fabricated of 16 gauge satincoat or stainless steel.
-
711mm in diameter with standard 254mm throat.
-
Fully assemble chute at the factory for installation.
-
Maximum of two sections per standard floor height.
-
Provide one expansion join per floor height.
-
Crimped joints are strictly prohibited.
-
All vertical seems shall be welded.
-
All doors attached to chute throats before delivery to jobsite.
|
-
Chute to be fabricated of 16 gauge satincoat or stainless steel.
-
610mm in diameter with standard 254mm throat.
-
Fully assemble chute at the factory for installation.
-
Maximum of two sections per standard floor height.
-
Provide one expansion join per floor height.
-
Crimped joints are strictly prohibited.
-
All vertical seems shall be welded.
-
All doors attached to chute throats before delivery to jobsite.
|
Intake door :
» Stainless steel door front with stainless steel trim.
» Noiseless self-closing by means of concealed closer.
» Bearing ULC 1 1/2 hour temperature rise 30 min. 121°C label. |
Bottom Hinged Door
Bottom hinged hand operated intake doors, or foot operated if desired, are recommendedfor most rubish chutes.
Standard dimension : 380mnm X 457mm |
|
Side Hinged door
Square side hinged intake doors are recommended for genral bagged linen applications.
Standard dimension : 457mm X 457mm
|
|
Discharge :
» Type "AC" according spring loaded horizontal fire damper. bearing ULC 1-1/2 hour label.
» Hopper discharge is available.
Sprinkler :
» Automatic sprinkler to be located in chute throats at top intake and alternating floors below.
Vent:
» To extend full diameter through to roof to a height of 1 meter.
» To be covered with a hinged rain cap with 10% air space for normal use and hold down quick release clips to allow 100% vent in case of fire.
Options :
» Disinfecting and sanitizing unit.
» Door inter locking.
» Flush spray head.
|
|